1. Core Substation Equipment & Standards
| Subsystem | Representative Rating / Role | Referenced Standards |
|---|---|---|
| Disconnectors | 27.5 kV, 1250 A rated normal current on copper alloy contacts | GB/T 1985-2023, TB/T 2803-2003 |
| Vacuum Circuit Breakers | Fault interruption and feeder zone switching | GB/T 1984, GB/T 11022 |
| Metal-Oxide Surge Arresters | Y5WT-42/120 class with 5 kA discharge class |
GB/T 11032 |
| Earthing & Touch Voltage | 60 V rms AC normal prospective touch voltage limit | EN 50122-1 / IEC 62128-1:2013 |
2. Feeding Architecture Options
The single-line diagram depends on feeding choice: plain 25 kV AC systems feed directly between catenary and rail, whereas 2×25 kV autotransformer (AT) systems deliver 50 kV between catenary and negative feeder with autotransformers installed every 10 to 15 km. DC railways instead deploy rectifier substations at closer intervals.
Source Documentation & Switchgear Catalog: